05/23/2019

Large-Room Occupancy Sensor Installation

TOPICS: Installation, Occupancy Sensors

To download the full installation guide, which includes detailed instructions & graphics for each step, click here.

To visit the 78003 Large-Room Occupancy Sensor Product Page, click here.


Large-room occupancy sensors should be placed in the approximate center of the room, with vents facing towards most likely points of entry or exit. Make certain there are no air vents within 4 feet of the sensor, and that no air is blowing across it. After selecting the optimal position for the occupancy sensor:

  • Remove the ceiling tile and cut a 1/2″-diameter hole in its center
  • Feed the sensor wires through the threaded rod, insert wide end of threaded rod into base of sensor, and twist to lock
  • Pass the threaded rod through the 1/2″ hole until sensor is flush with underside of ceiling tile
  • Pass wires through provided washer and nut, then tighten nut to secure sensor
  • Use provided wire nuts to connect as shown on cable label